Steam generator quality appraisal

Steam generator quality appraisal-Machinery & Equipment-CAS Testing Technical Services (Hong Kong) Company Limited

Steam generator qualityAppraisal Background

A steam generator is a device whose main function is to split water into steam in order to provide the required heat energy for various industrial processes and applications. Steam generators are widely used in many fields, such as energy, chemical industry, food processing, packaging machinery, medical pharmaceuticals, construction and building materials, etc. Its main function is to convert the thermal energy of water into steam energy to meet the thermal energy needs of various industrial processes and applications. As an important energy conversion equipment, steam generator plays an important role in many fields.
In steam generator quality appraisal cases, Zhongke Testing can provide steam generator quality appraisal services.

Steam generator qualityAppraisal Scope

Common types of steam generators include fuel steam generators, gas steam generators, electric steam generators, biomass steam generators, household steam generators, power station steam generators, industrial steam generators, high-pressure steam generators, low-pressure steam generators, medium-pressure steam generators, etc.

Steam generator qualityAccreditation criteria

NB/T 20508-2018 Steam generator heat transfer tube expansion tube profile eddy current detection
YY/T 0791-2018 Medical steam generator
SY/T 5854-2019 Oil field special wet steam generator safety specifications
NB/T 20526-2018 Factory hydraulic test requirements for pressurized water reactor steam generators

Steam generator qualityAuthentication case

A steam generator that was running in a company's boiler room exploded. The upper sealing plate of the steam generator was opened and separated from the sealing plates on both sides and the upper tube plate. The overflowing steam caused the collapse of two surrounding walls.
was entrusted by the court to conduct an appraisal and analysis on whether the steam generator involved in the case had quality problems that caused the explosion.
identification and analysis results: The
identification and analysis expert group discussed the relevant information and on-site investigation of the steam generator involved in the case and made a comprehensive quality and technical analysis, and made the following suggestions and conclusions:
1, the nominal material of the explosive steam generator is Q245R. The analysis results show that: the manganese element and aluminum element content are slightly low, the sulfur element content is slightly high, and the other element contents are normal.
2, the base material structure of this explosive steam generator is ferrite + pearlite, and there is no obvious abnormality in the structure.
3. The maximum deformation point of this explosion is the first crack. The inner fillet weld is not welded, and only the outer fillet weld serves as a connection. There is a welding defect here, and the effective thickness is about 2mm. Cracks propagate at the welding defects, resulting in insufficient effective wall thickness. Under the action of internal pressure in the steam generator, a one-time rapid cleavage fracture occurs.
Therefore, the cause of the accident was analyzed to be that a welding defect inside the steam generator product caused the equipment to explode. The nature of the accident was a general production safety liability accident.