Welcome to Hong Kong CAS Testing ~

lang  CN

Our Services

Quality appraisal of substation equipment

Quality appraisal of substation equipment-Machinery & Equipment-CAS Testing Technical Services (Hong Kong) Company Limited

Substation equipment qualityAppraisal Background

Transformation equipment is the core equipment of the substation, mainly including transformers and motors. Transformer is one of the most important equipment in a substation. It is used to step up and step down voltage to ensure that electrical energy is not lost due to excessive resistance loss during transmission. Electric motors are used to drive various equipment and machinery, such as pumps, fans, air compressors, etc.
In substation equipment quality appraisal cases, Zhongke Testing can provide substation equipment quality appraisal services.

Substation equipment qualityAccreditation criteria

GB/T 36291.1-2018 Technical specifications for configuration of power safety facilities Part 1: Substation
GB/T 37141.1-2022 Guidelines for ultraviolet imaging detection of electrical equipment in high altitude areas Part 1: Substation
GB/T 8286-2017 Mine explosion-proof mobile substation
GB/T 17467-2020 High-voltage/low-voltage prefabricated substation
GB/T 30155-2013 Technical guidelines for smart substations
GB/T 31239-2014 Technical specifications for 1000kV substation fittings
GB/T 40823-2021 Compact complete equipment for distribution substations (CEADS)
GB/T 25737-2010 Acceptance specification for 1000kV substation monitoring system
GB/T 24833-2009 Technical specification for 1000kV substation monitoring system
GB/T 40773-2021 Technical Specification for Substation Auxiliary Facilities Monitoring System
0GB 26860-2011 Electric Power Safety Work Regulations Electrical Parts of Power Plants and Substations
1GB/T 32893-2016 Operation and Management Specifications for Substation Operations of 10kV and Above Power Users
2GB/T 37137-2018 On-site inspection method for AC circuit system of Plateau 220kV substation
3GB/T 34925-2017 On-site inspection method for AC circuit system of Plateau 110kV substation
4

Substation equipment qualityAuthentication case

was entrusted by a public security bureau to conduct a quality analysis of the "substation equipment" involved in the case. The purpose of the quality appraisal analysis of the substation equipment is as follows:
(1) Whether the equipment, materials and configuration of the "substation equipment" involved in the case meet the contract requirements
(2) analyzes the causes of the power outage accident of the "substation equipment" involved;
(3) analyzes whether the "substation equipment" involved in the case violated national regulations and lowered project quality standards. The
expert team conducted an on-site inspection to investigate the post-accident status of the "substation equipment" involved, and simulated and calculated the causes of the accident. The quality appraisal opinions of the "substation equipment" were:
(1) Some equipment, materials and configurations in the high-voltage distribution facilities of the "substation equipment" involved did not comply with the provisions of the contract;
(2) Due to the lax sealing of the high-voltage switch cabinet involved and the improper configuration of the heating and dehumidification system, condensation inside the cabinet could not be effectively and reliably avoided, and the configuration and installation of the high-voltage switch cabinet did not meet standards, which ultimately led to the occurrence of a power outage accident for the "substation equipment" involved;
(3) The "substation equipment" involved did not meet the requirements of the contract and standards, and the quality of the product was reduced.